Back to all solutions
Solution 04 / 15

Smart Chiller

The chillers run hard all day, the cooling still falls short, and the bill doesn't move

What the screen looks like
Live · Secured
Chiller Efficiency
0.62kW/RT
146 RT
CHILLER-191 kW7.0 °CAHU / FCU146 RT12.4 °CDELTA-T5.4 KFLOW82 m³/hEFFICIENCY0.62 kW/RT
AI Insight8% saved

Delta-T has fallen to 5.4 K, below design — likely a valve held open at an AHU, returning water before it has done its work

Chiller CH-1
Modbus · Plant room
91 kW
CHW Supply / Return
PT100 · Header
7.0 / 12.4 °C
Flow Meter FM-1
Modbus · CHW main
82 m³/h
  • The loop: chiller, pump, and the load side
  • Supply and return temperature with the current Delta-T
  • Cooling load in tons against the power the chiller draws
  • kW per ton — the number that says how well the plant is doing

Figures on this screen are illustrative; a real one shows readings from your own site.

What you see

  • Nobody knows how much power goes in for the cooling that comes out
  • Delta-T below design: chilled water returns too warm-to-cold to do its work
  • Several chillers running when the load doesn't need them — noticed when the bill arrives

What we do

Chiller power, chilled-water supply and return temperatures and flow measured together, giving the real cooling load and the kW per ton, with a LINE alert when efficiency drops or Delta-T drifts.

What you get: You can see which chiller is the efficient one, how many to run at a given load, and what is pulling Delta-T down before a month's bill is spent.
Fits: Offices · Malls · Hotels · Hospitals · Factories

How it works

01
Sensors on the chilled-water loop

Supply and return temperature, flow rate, and each chiller's power

Modbus · BACnet
02
Gateway

Reads the meters and the chiller controller over Modbus or BACnet and sends it up

MQTT / HTTPS
03
Cloud

Every interval kept on servers in Thailand, so efficiency can be compared over time

History
04
AI analysis

Momosight compares kW per ton across chillers and load bands, and points at the hours Delta-T falls away

AI insight
05
Dashboard

Cooling load, power and efficiency for the whole plant on one screen

LINE · Email
06
Alerts and reports

LINE when efficiency slips, and a monthly report for the engineering team

The platform also speaksOPC UAPT1004GTelegram

What it does

Power per ton of cooling

Cooling worked out from measured flow and Delta-T, against measured power — kW per ton, from readings rather than a datasheet.

Delta-T watched continuously

A Delta-T below design means water circulating without doing its work; the system catches it as it happens.

Chiller against chiller

Which machine is the efficient one at which load — the basis for the staging order.

Real hourly cooling load

What the building actually needs through the day, so the right number of machines run.

Alerts and reports

LINE when readings drift, and a monthly efficiency report sent automatically.

Many buildings, one system

Compare efficiency between buildings or branches from one place.

Devices used in this system

Prices are per set; how many you need depends on the site.

Where it fits

Office buildings

Central chilled-water plant

Malls

Load that moves with trading hours

Hotels

Load that follows occupancy

Hospitals

Plant that cannot stop

Factories

Chilled water for process cooling

Convention centres and campuses

Peaks that come with events

How we work with you

  1. 01
    Survey the plant room

    The chillers and their sizes, the pumps, the pipework, and where sensors and a flow meter can go.

  2. 02
    Install and check

    Temperature sensors on supply and return, the flow meter and power meters fitted, then the readings verified.

  3. 03
    Design figures and limits

    The plant's design values, Delta-T and kW/ton thresholds, and the engineering team's LINE group.

  4. 04
    Support afterwards

    Annual MA, with efficiency reviewed on a cycle.

Related documents

Questions about this system

Does the plant have to be shut down to install it?

Temperature sensors strap to the pipe or use existing pockets. The flow meter depends on the type — some clamp outside the pipe with no cutting. We assess it on site and pick the least disruptive window.

Does it need to connect to the chiller controller?

Not necessarily. If the controller speaks Modbus or BACnet we read it too; if not, power, temperature and flow are all measured externally.

How is kW per ton calculated?

Cooling load from the measured flow and Delta-T, divided by the chiller's measured power over the same interval — all of it from readings, not from the machine's rating.

How much will it cut the bill?

It shows which chiller is efficient, how many should run, and what pulls Delta-T down. How much comes off depends on what the team changes; we do not promise a figure in advance.

Other solutions

LINE @momospaceReplies within 1 hr